| SAFE-T-THERM® PROPYLENE GLYCOL BASE HYDRONIC HEAT TRANSFER FLUID Comparative Corrosion Test Data - Using ASTM D1384 Text Method |
||||||
| SAFE-T-THERM®,1 | Boston Tap Water2 | Propylene
Glycol Uninhibited2,3 |
||||
| * | ** | * | ** | * | ** | |
| Copper | -13 | 0.5 | -10 | 0.4 | -2 | 0.1 |
| Solder | -10 | 0.3 | -140 | 5.6 | -750 | 3.0 |
| Brass | -3 | 0.1 | -10 | 0.4 | -2 | 0.1 |
| Steel | -22 | 0.8 | -300 | 14.7 | -1 | < 0.5 |
| Cast Iron | -4 | 0.2 | -570 | 24.1 | -1 | < 0.5 |
| Aluminum | -3 | 0.4 | -34 | 4.0 | -4 | 0.5 |
* Losses shown are in milligrams per test coupon
** Loss expressed in mills per year thickness of metal, approximate
Return to SAFE-T-THERM® Home Page
Return to Houghton Chemical Corp. Home Page
SAFE-T-THERM® is a registered trademark of Houghton Chemical Corporation